Features |
| |
| |
Module design for easy maintenance |
| |
Parallel Redundant Function (upto 8 sets) |
| |
Multi-CPU digital control to minimize electronic component |
| |
Intelligent multi-speed cooling fan control |
| |
Built-in SRAM upto 500 historical records & event log |
| |
Multi-language and user friendly graphic LCD display |
| |
Programable status, dry contact & RS232 & RS485 comm port |
| |
100% unbalanced and computer load suitability |
| |
Manual and scheduled battery test and battery replacement warning |
| |
Intelligent charger design to prolong battery lifetime |
| |
Local and remote emergency power-off (EPO) function |
| |
Common battery and hot standby function available |
| |
ISO 9001:2000 Certified |
|
|
 |
Specifications |
|
| |
| Capacity |
: |
| 20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
| 80KVA |
10OKVA |
120KVA |
160KVA |
200 KVA |
|
| AC Input |
|
|
| Voltage |
: |
| 220 V |
380 V |
230V - 400V |
240 V |
415V |
3Ø4W |
|
| Voltage Range |
: |
± 20% |
| Power Factor |
: |
> 0.95 (Full Load) |
| Frequency Range |
: |
50 / 60Hz + ±5Hz |
| AC Output |
|
|
| RMS Voltage 3/3 |
: |
220V / 380V, 230/ 400V, 240/415V 3Ø 4W |
| Static Regulation |
: |
±1% |
| Frequency with oscillator % |
: |
50Hz/60Hz±0.01 Hz |
| Frequency with synchronize % |
: |
50Hz/60Hz±1 Hz |
| Harmonic Distortion |
: |
< 3% Liner Load, < 5% Non - Liner Load |
| Wave Form |
: |
Pure Sine Wave |
| Overload Capacity |
: |
102% Continuous, 102%, 1 Minute, 125% - 150% 30 Seconds, > 150% : 2 Second |
| Crest Factor |
: |
3:1 |
| Efficiency |
|
|
| On Line Mode |
: |
90% |
| Economy Mode |
: |
97% |
| Battery Charger |
|
|
| DC BUS |
: |
240VDC / 348VDC / 384VDC * |
| Battery Type |
: |
VRLAType Sealed Lead Acid Maintenance Free/Tubular/Flat Plate Tubular/Nickel Cadmium * |
| Recharge Time |
: |
6 to 8 Hrs. to 90% |
| Function |
|
|
| Parallel Redundant |
: |
Yes (Upto 8 UPS) ** |
| SRAM Fault Sequence Memory |
: |
Yes |
| Programmable Parameter Setting |
: |
Yes |
| Battery Start Function |
: |
Yes ** |
| Operation |
|
|
| Static Bypass Operation |
: |
|
| Inverter to Bypass |
: |
< 1 ms |
| Bypass to Inverter |
: |
< 1 ms |
| Transient Response |
: |
±5%, 10ms |
| Audible Noise |
: |
<60dB |
| Alarms |
: |
Load on Battery - Discontinuous Alarm /UPS abnormal - Continuous Alarm |
| LED Status Indications |
: |
AC Mains Normal/Reserve Source Normal/Rectifier/Inverter/Static Switch and Battery Status Indication. |
| LCD Display |
: |
Input, Bypass , Inverter, Output & Battery Voltage, Current and Frequency Load Level Display |
| Interface |
|
|
| Communication Interface |
: |
Standard RS232, Dry Contact, IBM AS/400 |
| SNMP |
: |
Optional |
| Remote Emergency Power OFF |
: |
Optional |
| Mechanical |
|
|
| *User choice **On request |
|
|